Concentrator

Primarily using Type II concentrators, in accordance with State Grid’s standard application scenarios and specifications, the meter‑reading device must continue to operate for 1 minute after a power outage. Its typical current consumption is approximately 200 mA, with a nominal operating voltage of 5 V. Supercapacitors are chosen as a replacement for batteries because, in outdoor environments, battery performance degrades rapidly, resulting in a service life that cannot match the overall equipment lifespan. Moreover, supercapacitors can reliably supply the pulsed currents required for 4G, GPS, and carrier‑communication functions. Commonly selected models include 2.7 V–25 F, 2.7 V–20 F, 2.7 V–16 F, and 2.7 V–10 F; the industry‑standard approach is to connect two individual cells in series, typically using two 2.7 V–25 F units.

Consultation